Outdoor Temperature Sensor Belimo
For measuring temperature in outdoor areas. Typical applications at cold stores, greenhouses, production plants and warehouses. NEMA 4X / IP65 rated enclosure.
For measuring temperature in outdoor areas. Typical applications at cold stores, greenhouses, production plants and warehouses. NEMA 4X / IP65 rated enclosure.
This device has been designed for use in stationary heating, ventilation and air-conditioning systems and must not be used outside the specified field of application. Unauthorised modifications are prohibited. The product must not be used in relation with any equipment that in case of a failure may threaten humans, animals or assets.
Ensure all power is disconnected before installing. Do not connect to live/operating equipment. Only authorised specialists may carry out installation. All applicable legal or institutional installation regulations must be complied during installation.
The device contains electrical and electronic components and must not be disposed of as household refuse. All locally valid regulations and requirements must be observed.
Electrical connection Removable spring loaded terminal block max. 2.5 mm²
Cable entry Cable gland with strain relief Ø6...8 mm
Application Air
Measuring values Temperature
Time constant τ (63%) in the room Typical 854 s
Cable gland PA6, white
Mounting plate Lexan, grey RAL7001
Housing Cover: Lexan, white
Bottom: Lexan, white
Seal: 0467 NBR70, black UV resistant
Safety data
Ambient humidity Max. 95% r.H., non-condensing
Ambient temperature -35...50°C [-30...120°F]
Fluid temperature -35...50°C [-30...120°F]
Housing surface temperature Max. 90°C [195°F]
Protection class IEC/EN III Safety Extra-Low Voltage (SELV)
Protection class UL UL Class 2 Supply
EU Conformity CE Marking
Certification IEC/EN IEC/EN 60730-1
Degree of protection IEC/EN IP65
Degree of protection NEMA/UL NEMA 4X
Quality Standard ISO 9001
#BBD0E0 »